Schneider TSXCTY4AC 4-Channel Counter Module - 40 kHz Frequency, 36 mA at 24 V DC, 330 mA at 5 V DC
Product Description
Schneider TSXCTY4AC 4-Channel Counter Module - 40 kHz, 36 mA at 24 V DC, 330 mA at 5 V DC
Enhance your automation and control systems with the Schneider TSXCTY4AC 4-Channel Counter Module, a high-performance solution designed for precision counting applications. This advanced module is engineered to support up to four independent counting channels, making it ideal for complex, multi-channel counting tasks in industrial environments.
Key Features:
High-Frequency Counting: Capable of handling input frequencies up to 40 kHz, the TSXCTY4AC ensures accurate and reliable counting for high-speed applications. This makes it suitable for use in processes where fast and precise counting is crucial.
Versatile Input Range: The module operates efficiently with a current consumption of 36 mA at 24 V DC and 330 mA at 5 V DC, providing flexibility in various control system configurations. Its adaptable power requirements make it compatible with different voltage levels, enhancing its integration into existing setups.
Compact and Robust Design: Engineered by Schneider Electric, this module features a compact footprint that integrates seamlessly into your control system, minimizing space requirements while maximizing performance. Its robust design ensures reliable operation even in demanding industrial environments.
Advanced Counting Capabilities: The TSXCTY4AC is designed to handle a wide range of counting tasks, from simple batch counting to complex multi-axis measurement systems. Its advanced functionality supports precise data acquisition and processing, essential for optimizing your automation processes.
Ease of Integration: Designed for compatibility with Schneider Electric's automation systems, the TSXCTY4AC module integrates smoothly with other components, providing a cohesive solution for your industrial control needs. Its straightforward installation and configuration process ensures quick setup and minimal downtime.
Applications:
The Schneider TSXCTY4AC 4-Channel Counter Module is ideal for use in various industrial applications, including:
- Manufacturing Automation: For accurate counting in production lines and batch processing.
- Process Control: To monitor and control high-speed processes and systems.
- Machine Tools: For precise measurement and monitoring in CNC machinery and other automated equipment.
Technical Specifications:
- Channels: 4
- Maximum Frequency: 40 kHz
- Current Consumption: 36 mA at 24 V DC, 330 mA at 5 V DC
- Compatibility: Schneider Electric automation systems
Optimize your industrial automation with the Schneider TSXCTY4AC 4-Channel Counter Module, delivering precision, reliability, and flexibility for your most demanding counting applications. Contact us today to learn more about integrating this advanced module into your control system.
range of product |
Modicon Premium Automation platform
|
|
---|---|---|
product or component type |
Counter modules
|
|
I/O modularity |
4 channels
|
|
electrical circuit type |
Auxiliary output
|
counting frequency |
40000 Hz
|
|
---|---|---|
power dissipation in W |
8...11.5 W
|
|
cycle time |
10 ms
|
|
discrete input logic |
Current sink auxiliary input (preset, enable and read)
conforming to IEC 1131 Type 2
Resistive 2/3-wire proximity sensors PNP/NPN conforming to IEC 1131 Type 2 Resistive encoder input |
|
input logic |
Positive
|
|
input compatibility |
Incremental encoder 10...30 V totem pole
Incremental encoder 5 V DC RS422 |
|
input voltage |
24 V 18 mA 2/3-wire proximity sensors PNP/NPN
24 V 7 mA auxiliary input (preset, enable and read) 5 V 18 mA encoder input |
|
input voltage limits |
<= 5.5 V encoder input
19...30 V 2/3-wire proximity sensors PNP/NPN 19...30 V auxiliary input (preset, enable and read) |
|
voltage state 1 guaranteed |
>= 11 V 2/3-wire proximity sensors PNP/NPN
>= 11 V auxiliary input (preset, enable and read) >= 2.4 V encoder input |
|
current state 1 guaranteed |
>= 3.7 mA encoder input
>= 6 mA 2/3-wire proximity sensors PNP/NPN >= 6 mA auxiliary input (preset, enable and read) |
|
voltage state 0 guaranteed |
<= 1.2 V encoder input
<= 5 V 2/3-wire proximity sensors PNP/NPN <= 5 V auxiliary input (preset, enable and read) |
|
current state 0 guaranteed |
<= 1 mA encoder input
<= 2 mA 2/3-wire proximity sensors PNP/NPN <= 2 mA auxiliary input (preset, enable and read) |
|
response time |
< 2.5 ms sensor voltage at loss of 24 V auxiliary input (preset,
enable and read)
|
|
input impedance |
> 270 Ohm at U = 2.4 V encoder input
1400 Ohm at Un 2/3-wire proximity sensors PNP/NPN 3400 Ohm at Un auxiliary input (preset, enable and read) 400 Ohm at Un encoder input |
|
output voltage |
24 V DC
|
|
nominal output current |
0.5 A
|
|
output voltage limits |
19...30 V
|
|
voltage drop |
< 0.5 V at state 1
|
|
output compatibility |
Positive logic DC inputs (resistance <= 15 kOhm) auxiliary
output
|
|
leakage current |
< 0.1 mA
|
|
switching time |
< 0.25 ms
|
|
switching frequency |
< 0.6/LI² Hz on inductive load
|
|
output overload protection |
Current limiter
Thermal tripping via program or automatically |
|
output short-circuit protection |
Current limiter
Thermal tripping via program or automatically |
|
output overvoltage protection |
Zener diode
|
|
reverse polarity protection |
Reverse diode on supply
|
|
checks |
Sensor power supply
|
|
current consumption |
330 mA 5 V DC
36 mA 24 V DC |
|
module format |
Standard
|
|
local signalling |
4 LEDs green axis diagnostics available (CH.)
1 LED green module operating (RUN) 1 LED red external fault (I/O) 1 LED red internal fault, module failure (ERR) |
|
electrical connection |
2 connectors HE-10 20 pins
4 connectors SUB-D 15 |
|
product weight |
0.43 kg
|
protective treatment |
Conformal coating Humiseal 1A33
TC |
|
---|---|---|
ambient air temperature for operation |
0...60 °C
|
|
ambient air temperature for storage |
-25...70 °C
|
|
relative humidity |
5...95 % without condensation
|
|
operating altitude |
<= 2000 m
|
When you order from opencartworks.com, you will receive a confirmation email. Once your order is shipped, you will be emailed the tracking information for your order's shipment. You can choose your preferred shipping method on the Order Information page during the checkout process.
The total time it takes to receive your order is shown below:
The total delivery time is calculated from the time your order is placed until the time it is delivered to you. Total delivery time is broken down into processing time and shipping time.
Processing time: The time it takes to prepare your item(s) to ship from our warehouse. This includes preparing your items, performing quality checks, and packing for shipment.
Shipping time: The time for your item(s) to tarvel from our warehouse to your destination.
Shipping from your local warehouse is significantly faster. Some charges may apply.
In addition, the transit time depends on where you're located and where your package comes from. If you want to know more information, please contact the customer service. We will settle your problem as soon as possible. Enjoy shopping!