The Schneider TM3DM24R Module TM3 - 24 IO Relays is a high-performance, versatile expansion module designed to enhance the capabilities of your Schneider Electric automation systems. Engineered to deliver exceptional reliability and operational efficiency, this module offers 24 digital relay outputs, providing robust and flexible control over various industrial applications.
The Schneider TM3DM24R Module is ideal for use in various applications including:
Schneider Electric's TM3DM24R Module represents the pinnacle of industrial relay technology, offering unmatched reliability, performance, and ease of use. With Schneider Electric’s legacy of innovation and quality, you can trust that the TM3DM24R will deliver exceptional value and performance for your automation needs.
For more information or to request a quote, please contact us or visit our website.
range of product |
Modicon TM3
|
|
---|---|---|
product or component type |
Discrete I/O module
|
|
range compatibility |
Modicon M241
Modicon M251 Modicon M221 |
|
discrete input number |
16 input conforming to IEC 61131-2 Type 1
|
|
discrete input logic |
Sink or source (positive/negative)
|
|
discrete input voltage |
24 V
|
|
discrete input current |
7 mA for input
|
|
discrete output type |
Relay normally open
|
|
discrete output number |
8
|
|
discrete output logic |
Positive or negative
|
|
discrete output voltage |
24 V DC for relay output
240 V AC for relay output |
|
discrete output current |
2000 mA for relay output
|
discrete I/O number |
24
|
|
---|---|---|
current consumption |
5 mA at 5 V DC via bus connector at state off
0 mA at 24 V DC via bus connector at state on 0 mA at 24 V DC via bus connector at state off 65 mA at 5 V DC via bus connector at state on |
|
discrete input voltage type |
DC
|
|
voltage state 1 guaranteed |
15...28.8 V for input
|
|
current state 1 guaranteed |
>= 2.5 mA for input
|
|
voltage state 0 guaranteed |
0...5 V for input
|
|
current state 0 guaranteed |
<= 1 mA for input
|
|
input impedance |
3.4 kOhm
|
|
response time |
4 ms for turn-on
4 ms for turn-off |
|
current per output common |
7 A
|
|
mechanical durability |
20000000 cycles
|
|
minimum load |
10 mA at 5 V DC for relay output
|
|
local signalling |
1 LED per channel green for I/O state
|
|
electrical connection |
Removable screw terminal block pitch 3.81 mm with 17 terminal(s)
of 1.5 mm² connection capacity for inputs
Removable screw terminal block pitch 3.81 mm with 11 terminal(s) of 1.5 mm² connection capacity for outputs |
|
insulation |
Non-insulated between inputs
500 V AC between output and internal logic Non-insulated between outputs 500 V AC between input and internal logic 1500 V AC between input groups and output groups 750 V AC between open contact |
|
marking |
CE
|
|
mounting support |
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715 Plate or panel with fixing kit |
|
height |
90 mm
|
|
depth |
84.6 mm
|
|
width |
42.9 mm
|
standards |
EN/IEC 61131-2
EN/IEC 61010-2-201 |
|
---|---|---|
product certifications |
C-Tick
cULus |
|
resistance to electrostatic discharge |
4 kV (on contact) conforming to EN/IEC 61000-4-2
8 kV (in air) conforming to EN/IEC 61000-4-2 |
|
resistance to electromagnetic fields |
10 V/m at 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m at 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3 1 V/m at 2 GHz...3 GHz conforming to EN/IEC 61000-4-3 |
|
resistance to magnetic fields |
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
|
|
resistance to fast transients |
2 kV for relay output conforming to EN/IEC 61000-4-4
1 kV for I/O conforming to EN/IEC 61000-4-4 |
|
surge withstand |
1 kV for input in common mode conforming to EN/IEC 61000-4-5
2 kV for output in common mode conforming to EN/IEC 61000-4-5 |
|
resistance to conducted disturbances |
10 Vrms at 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 Vrms at spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
|
electromagnetic emission |
Radiated emissions, test level: 40 dBμV/m QP with class A,
condition of test: 10 m (radio frequency: 30...230 MHz)
conforming to EN/IEC 55011
Radiated emissions, test level: 47 dBμV/m QP with class A, condition of test: 10 m (radio frequency: 230...1000 MHz) conforming to EN/IEC 55011 |
|
ambient air temperature for operation |
-10...55 °C for horizontal installation
-10...35 °C for vertical installation |
|
ambient air temperature for storage |
-25...70 °C
|
|
relative humidity |
10...95 % without condensation in operation
10...95 % without condensation in storage |
|
IP degree of protection |
IP20 with protective cover in place
|
|
pollution degree |
2
|
|
operating altitude |
0...2000 m
|
|
storage altitude |
0...3000 m
|
|
vibration resistance |
3.5 mm (vibration frequency: 5...8.4 Hz) on DIN rail
3 gn (vibration frequency: 8.4...150 Hz) on DIN rail 3.5 mm (vibration frequency: 5...8.4 Hz) on panel 3 gn (vibration frequency: 8.4...150 Hz) on panel |
|
shock resistance |
15 gn (test wave duration:11 ms)
|
There are no reviews for this product.