Schneider TCSEGDB23F24FK Modbus Plus Proxy Module for Modicon M340 PLC - Coated

Schneider TCSEGDB23F24FK Modbus Plus Proxy Module for Modicon M340 PLC - Coated

0 reviews 0 sold. Only 1000 remain
Brand:
Product Code: TCSEGDB23F24FK
Availability: 1000
Viewed 1464 times

Product Description

Schneider TCSEGDB23F24FK Modbus Plus Proxy Module for Modicon M340 PLC

Overview

The Schneider TCSEGDB23F24FK Modbus Plus Proxy Module is an advanced interface solution designed to seamlessly integrate Modbus Plus networks with Schneider Electric's Modicon M340 PLC systems. This module serves as a critical component in bridging legacy Modbus Plus communication protocols with modern automation systems, enhancing connectivity and data exchange capabilities within complex industrial environments.

Key Features

  • Modbus Plus Integration: Facilitates communication between Modbus Plus networks and Modicon M340 PLC systems, ensuring smooth and reliable data transfer between legacy and contemporary control systems.

  • Enhanced Connectivity: Offers robust and stable connectivity, allowing for efficient data exchange and control across various industrial applications.

  • Coated for Durability: The module features a protective coating, providing superior resistance to environmental factors such as dust, moisture, and corrosive elements. This ensures reliable operation even in harsh industrial conditions.

  • Seamless Configuration: Designed for easy configuration and integration with Modicon M340 PLCs, minimizing setup time and reducing the complexity of system integration.

  • High-Performance Communication: Delivers high-speed data transmission with minimal latency, supporting real-time data processing and control.

  • Durable Construction: Built with high-quality materials to withstand industrial environments, ensuring longevity and consistent performance.

Technical Specifications

  • Protocol Compatibility: Modbus Plus
  • PLC Compatibility: Modicon M340
  • Protection: Coated for enhanced durability
  • Data Transmission Speed: High-speed communication
  • Operating Environment: Suitable for harsh industrial conditions

Applications

The Schneider TCSEGDB23F24FK is ideal for use in industries where legacy Modbus Plus systems need to interface with modern Modicon M340 PLC systems. Typical applications include manufacturing automation, process control, and any environment requiring reliable communication between different generations of control systems.

Benefits

  • Future-Proof Integration: Enables integration of older Modbus Plus systems with new Modicon M340 PLCs, protecting your existing investments while upgrading your control system capabilities.
  • Increased Reliability: The coated design enhances durability, reducing maintenance needs and extending the module's operational life.
  • Efficient Data Handling: High-performance communication ensures efficient data handling and control, improving overall system efficiency.

Conclusion

The Schneider TCSEGDB23F24FK Modbus Plus Proxy Module is a pivotal component for modernizing and enhancing communication in automation systems. Its robust design, ease of integration, and advanced features make it a valuable asset for bridging legacy systems with contemporary PLC technology. Enhance your automation infrastructure with Schneider's reliable and efficient solution.

Main
range of product
Modicon M340 automation platform
product or component type
Modbus Plus proxy module
structure type
Industrial bus
Complementary
communication gateway
Ethernet Modbus TCP to Modbus Plus
product compatibility
M340 PLC
physical interface
10/100BASE-T
RS485
method of access
Token ring (Modbus Plus)
CSMA/CD (Modbus TCP)
transmission support medium
Single twisted pair cable (Modbus Plus)
Category 5 shielded twisted pair (STP) (Modbus TCP)
transmission rate
1 Mbit/s for bus length of 450 m per segment (Modbus Plus)
1 Mbit/s for bus length of 1800 m with 3 repeaters (Modbus Plus)
10...100 Mbit/s for bus length of 100 m without repeater (Modbus TCP)
number of slave
128
communication service
Modbus Plus messaging
Configuration control
Diagnostics
Modbus Plus server (scanned by the PLC)
FDR
SNMP network management
Read/write variables
Peer cop dialogue
Global Data
Modbus TCP messaging
integrated connection type
2 Ethernet TCP/IP with RJ45 (Modbus TCP)
2 Modbus with SUB-D 9 (Modbus Plus)
current consumption
300 mA at 24 V DC external supply
module format
Standard

Environment
ambient air temperature for operation
-25...70 °C
ambient air temperature for storage
-45...85 °C
relative humidity
10...95 % without condensation
operating altitude
<= 2000 m
protective treatment
Conformal coating Humiseal 1A33

Write a review

Please login or register to review

When you order from opencartworks.com, you will receive a confirmation email. Once your order is shipped, you will be emailed the tracking information for your order's shipment. You can choose your preferred shipping method on the Order Information page during the checkout process.

The total time it takes to receive your order is shown below:

The total delivery time is calculated from the time your order is placed until the time it is delivered to you. Total delivery time is broken down into processing time and shipping time.

Processing time: The time it takes to prepare your item(s) to ship from our warehouse. This includes preparing your items, performing quality checks, and packing for shipment.

Shipping time: The time for your item(s) to tarvel from our warehouse to your destination.

Shipping from your local warehouse is significantly faster. Some charges may apply.

In addition, the transit time depends on where you're located and where your package comes from. If you want to know more information, please contact the customer service. We will settle your problem as soon as possible. Enjoy shopping!

Size Chart